OPERATION&MAINTENANCEMANUALTC670RRRefrigerant Recycling CenterRTI Technologies, Inc.10 Innovation DriveP.O. Box 3099York, PA 17402 USA717-840-0678
Page 9PARTS IDENTIFICATIONP/N DESCRIPTION1 024-80066-00 Rocker Switch (Visi-Red)2 025-80135-00 Indicator Light (Red) 250 VAC3 026-80071-02 High Side G
Page 10FLOW DIAGRAM 570-80286-00670RR FLOW (2004)January 17, 2005
Page 11SCHEMATIC DIAGRAM ONOFFONOFFONOFFOFFON570-80313-00670RR SCHEMATIC (2004)January 31, 2005
Page 12EC Declaration of Conformity for MachineryDirective 98/37/ECRTI Technologies, Inc.10 Innovation DriveYork, Pennsylvania 17402 USAPhone: 717-840
TABLE OF CONTENTSTC670RRStart Up & Safety Operation ...2Recover - Recycle ...3Oil Drain & Air Purge ...
Page 2STARTUP & SAFE OPERATION9 Do not use a damaged unit. Check for shipping damage and place a claim with carrier ifdamage is discovered.9 The T
Page 3RECOVER - RECYCLETo Recover - Recycle, refer to the above illustration and follow these steps:1. Attach the Red and Blue Hoses to the A/C system
Page 4NON-CONDENSABLE PURGE CHART(BARS)0C R12 R22 R502 R134a R410A R407C0 3.03 5.45 6.34 2.90 10.27 7.381 3.15 5.63 6.59 3.01 10.62 7.652 3.28 5.79 6.
Page 5VACUUMIf the A/C System is "opened" for replacing components, it is important to draw a vacuum onthe system before recharging with ref
Page 6SELF EVACUATIONThe TC670RR can be used for different refrigerant types. The unit needs to be cleared of onerefrigerant before introducing anothe
Page 7VERY IMPORTANTThe TC670RR requires that 2 ounces (60ml) of compressor oil be added afterevery 25 hours of operation. This oil replaces the oil r
Page 8TC670RR Rear Layout.dwg12546783109COMPONENT SETUP1 - Long Filter (026-80077-00)2 - Anti-blowback Valve on Hose3 - Yellow Hose4 - Oil Drain5 - Sh